Herunterladen Inhalt Inhalt Diese Seite drucken

Trox FSL-CONTROL II Installations- Und Konfigurationsanleitung Seite 58

Einzelraumregelung
Inhaltsverzeichnis

Werbung

Konfiguration Schnittstellen / GLT
BACnet MS/TP Schnittstelle
Configuration Switches
Hexadecimal Switches X, Y
DIP Switch 2
DIP Switch 3
Baudrate
Device Object
Property
Object_Identifier
Object_Name
Object_Type
System_Status
Vendor_Name
Vendor_Identifier
Model_Name
Firmware_Revision
Application_Software_Version
Protocol_Version
Protocol_Revision
Protocol_Services_Supported
Protocol_Object_Types_Supported
Object_List
Max_APDU_Length_Accepted
Segmentation_Supported
APDU_Timeout
Number_Of_APDU_Retries
Device_Address_Binding
Database_Revision
Description
Max_Master
Max_Info_Frames
R: Read Property, W: Write Property, -E: Storage in EEPROM
PICS_X-AIRCONTROL_v1.0.doc
58
Network-Address
OFF
ON
OFF
OFF
OFF
ON
9600
19200
38400
Remark / Value
device, default instance: 32900 + Address Switch
max. 50 Bytes, default "EM-BACnet"
DEVICE (8)
OPERATIONAL (0)
"TROX GmbH"
329
"EM-BAC-MOD-01 FSLII"
"1.0"
"1.0"
1
12
read-property, write-property, device-communication-control,
reinitialize-device, who-has, who-is
DEVICE, ANALOG_VALUE, BINARY_VALUE,
MULTISTATE_VALUE
device, analog-value 1...18,
binary-value 1...20, multistate-value 1...9
480
NO_SEGMENTATION (3)
3000
0
-
0
Controller Type "FSL-CONTROL II"
default 127
default 1
Einzelraumregelung FSL‑CONTROL II
ON
ON
76800
- 3 -
RW
RW-E
RW-E
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
RW-E
RW-E

Werbung

Inhaltsverzeichnis
loading