Lighting and / or an advance warning light (optional)
The control is provided with 2 relay outputs by means of which
the lighting or the advance warning light is switched (menu
items 45 and 46).
External control devices / pulse generators (optional)
The door can be opened and closed by external control devices /
pulse generators.
Radio hand-held transmitter (optional)
The operating mode for the radio hand-held transmitter can be
selected in menu 6 – menu item 64.
Start button (functional process in pulse OPEN operating mode /
pulse CLOSE):
•
Initial pulse generation:
Drive starts and moves the door to the end position OPEN
or CLOSE that is set.
•
Pulse generation during the process:
Door stops.
•
New pulse:
Door continues moving in the opposite direction.
AR operation:
•
Pulse generation: Door opens
½ door opening button
•
Function as for the start button, however, the door only
approaches the ½ door opening that is set.
Light button:
•
The light function is a continuous light, which can be
switched irrespective of the "ON / OFF" door action.
Key switch function (optional)
The control is provided with an input for a key switch. This allows
you to activate various functions using menu item 50, "Key switch
function".
Door action status display
Display State
Upper end position OPEN reached
Door end position has not been reached
Lower end position CLOSE reached
Representation of the door opening frequency
Representation of the door closing frequency
Inner segment display flashes: Timer for automatic
closing is active
or
Control is ready to operate
Only in AR operation: continuous start detected at
input terminals J1, J7 or J8
Force learning cycle is carried out (menu item 48).
8
Troubleshooting
Error
State
E01
Door settings cannot be
set
E02
Door neither opens nor
closes. Safety in-
put J4.3/4 triggered
E03
Door neither opens nor
closes. Wicket door open
E04
Door opens slowly
E05
Door neither opens nor
closes. Safety switch has
triggered
E06
Door reverses / does not
close
E07
Door reverses / does not
close
E08
Door neither opens nor
closes. DES safety circuit
drive open
E09
Door neither opens nor
closes
E10
Menu item 36 set to
value 3 or 4
E11
Door neither opens nor
closes. Slack rope switch
has triggered
E91
Door neither opens nor
closes. Continuous STOP
command detected
F01
No door movement
F2
No response
F3
F4
F5
Reset has been executed Check mains environment
F19
Door responds only to
dead man's control for
closing
F20
Door responds only to
dead man's control for
closing
F21
Brief operational interrup-
tion
T100 R-FU 1,5kW
Diagnosed cause
Drive motor has not been se-
lected. Menu setting [79].
Check status of the peripher-
als at J4.3/4.
Close wicket door.
Anti-crash sensor triggered.
Check door/door guide.
Connection line 8k2 strip
damaged, check slack rope
switch.
Closing edge has triggered.
Check menu item 35.
Photoelectric sensor has
triggered. Check menu
item 36.
Manual override actuated,
Motor, thermal switch has
triggered, motor overload or
blockage.
No door end position pro-
grammed.
Program door end position
under menu items 30 + 31.
Completely open and close
door to determine the position
of the photoelectric sensor.
Check ropes.
Check STOP button at J1.
Stop membrane key actu-
ated.
Faulty feedback for brake re-
lay.
Error occurred during self-
testing. Replace control.
with regard to electrical dis-
turbance sources, increase
distance of motor cable and /
or signal lines to mains
cables, actuate start button
on control for normal opera-
tion.
Closing edge testing has
failed. Check closing edge
safety device.
Testing of photoelectric
sensor has failed. Check pho-
toelectric sensor.
Door movement exceeded
time value detected (90 sec).
Check door for ease of mo-
tion or blockage. Check end
positions.
EN - 33