Error
State
F23
No response
F24
No response to start com-
mand
F27
Drive blocked
F28
No response to start com-
mand
F29
Motor rotates in incorrect
direction.
F30
Door only runs in dead
man mode for closing
F31
Door neither opens nor
closes
F33
Door stops during the
opening process
F34
Door neither opens nor
closes
F35
Door neither opens nor
closes
F36
Door neither opens nor
closes
F39
No response
F40
Extended control does
not respond
F41
Extended control does
not respond
F42
Extended control does
not respond
F43
Extended control does
not respond
F45
RSE, wireless closing
edge
F46
RSE, wireless closing
edge
F47
Error detected during in-
ternal testing of the safety
circuit.
34 - EN
Diagnosed cause
Electronic door lock EDL100
is not responding. Check wir-
ing. Locking bolt is jammed,
check locking bolt for ease of
motion. Do not apply oil or
grease to door locking.
No connection to the DES.
Check motor connection
cable and DES.
Check door mechanics /
check phases, motor connec-
tion cable.
Voltage supply error. Check
mains connection. Check
peripherals for short circuit.
Mains phases have been in-
verted. Correct or re-adjust.
Return from pulsed operation
to dead man mode. Check
closing edge safety device
and photoelectric sensor.
Button actuated. Continuous
pulse pending. Check ex-
ternal control devices (J1).
Opening force limitation has
tripped. Door can only be
closed in dead man mode.
Eliminate sluggishness or
blockage of the door. Check
springs. Eliminate the cause
of the excessive force, then
open and close the door.
Duty cycle exceeded. Wait
and let motor cool down.
Speed monitor has tripped.
Check the selected motor
type and brake in menu 78,
79. Readjust brake ramps
and speeds.
Fault with internal communic-
ation between control and fre-
quency converter. Check con-
nection at terminal J10.
The (multi-turn) position
sensor's battery is low. Ex-
change position sensor.
24 V failed. Check connec-
tions on extended control.
Error occurred during self-
testing. Replace extended
control.
Error occurred during self-
testing. Replace extended
control.
No connection.
Module is not available, at-
tach.
Replace battery.
Pull out the mains plug, then
plug it back in.
T100 R-FU 1,5kW
Error
State
F71
Door neither opens nor
closes. Erroneous wicket
door contact.
F72
Door neither opens nor
closes
F73
Door neither opens nor
closes. Testing of in-
put J4.1/2 failed
F74
Door neither opens nor
closes. Testing of in-
put J4.3/4 failed
F75
Door neither opens nor
closes. Output voltage J4
erroneous
F76
Door neither opens nor
closes. Invalid sensors
J4.1/2 detected
F77
Door neither opens nor
closes. Invalid sensors
J4.3/4 detected
F78
Drive blocks in end posi-
tion CLOSE
If the safety circuit is in-
terrupted, the warning in-
dicator is illuminated, see
troubleshooting.
Other frequency converter-specific error displays
Error
State
F56
Door neither opens nor
closes
F57
Door neither opens nor
closes
F60
Door neither opens nor
closes
Diagnosed cause
Check contact resistances.
Check assembly of the wicket
door contact. Open and close
wicket door, check assembly.
Short circuit detected in the
safety circuit wicket door con-
tact / slack rope switch
J4.1/2. Check cables for short
circuit, eliminate short circuit.
Switch control on and off. If
necessary, replace control.
Switch control on and off. If
necessary, replace control.
Switch control on and off.
Check closing edge safety
device, door connection box
for short circuit. Check ter-
minal assignment.
Check resistors. Check
sensors.
Check resistors. Check
sensors.
Check spring tension, check
door mechanics, check
CLOSE end position.
Diagnosed cause
Overcurrent on IGBT
module
Overtemperature frequency
converter
Motor connection interrupted