Crush hazard and risk of being struck by the
CAUTION
closing door
The pressure wave switches may only be actu-
ated after having been tested.
•
For this purpose, select the value 2 in menu
item 35.
b
Fig.
Connect a door connection box with a break-away sensor
and an OSE (optical closing edge safety device).
c
Fig.
Connect a door connection box with a break-away sensor
and an 8k2 closing edge safety device).
When using a RSE module, a light grid or another safety
solution, connect the 8k2 resistor directly to terminal J3. Value 1
has to be selected in menu item 35.
11. Light grid
Danger due to missing monitoring of the
CAUTION
movement area in AR operation
When using a light grid with "blanking function" in
AR operation, additional monitoring of the move-
ment area must be provided.
Instead of the closing edge safety device, the following light grids
can be connected:
a
Fig.
A light grid by Telco with "SG14" testing. Set the value
to 1 in menu item 36.
b
Fig.
A light grid by Telco with "SG15" OSE interface. Set the
value to 0 in menu item 35.
c
Fig.
A light grid by CEDES with "GridScan/Mini-SB-2" OSE in-
terface. Set the value to 0 in menu item 35.
d
Fig.
A light grid by WITT with "LIGI" OSE interface. Set the
value to 0 in menu item 35.
12. Photoelectric sensor
Connect the photoelectric sensor as specified for the following
variants:
a
Fig.
2-wire photoelectric sensor LS2
b
Fig.
4-wire photoelectric sensor LS5 with testing
c
Fig.
Reflection photoelectric sensor
Then select the corresponding photoelectric sensor under menu
item 36.
If you have selected the value 3 "Photoelectric sensor mounted in
the frame", the next CLOSE run executed by the control is a
"learning cycle" for detecting the position.
Do not interrupt the learning cycle for
NOTICE
detecting the position of the photoelectric
sensors
The automatic position detection of the installed
photoelectric sensor must not be interrupted.
13. Anti-crash sensor
Via a connected anti-crash sensor, input J6 detects when the cur-
tain is off guide and starts automatic threading up.
a
Fig.
One-way light barrier (SMR32xx / SMT30xxC)
b
Fig.
One-way light barrier (ELS-300 NO)
14. STOP circuit
a
Fig.
Emergency stop connection
Connect the emergency stop button to terminal J4.3/4.
b
Fig.
Connection of the roll-up protection mechanism
To provide for protection from being drawn in, with fixed cable
routing a roll-up protection mechanism with an evaluation unit can
be connected to the safety circuit J4.3/4. The evaluation unit must
comply with PL c Cat3 as per EN 13849-1.
Also use this input to connect a spring break switch.
24 - EN
15. Key switch
When connecting a key switch to the connection terminal J7 (see
illustration), the control has to be programmed accordingly. Select
the desired function in menu item 50 "Key switch function".
16. Radio receiver
For the use of a hand-held transmitter, attach the receiver module
(option) to J11 as shown in the illustration and connect the an-
tenna to J12. In order to program the hand-held transmitters, fol-
low the instructions provided in Programming a radio hand-held
transmitter in the Programming chapter.
17. Relay outputs
The control provides two potential-free change-over contacts
(250 V AC / 2 A, 24 V DC / 1 A).
The 24 V output at terminal X8 may be loaded with a maximum of
700 mA.
Select the desired relay function in menu items 45 and 46.
a
Fig.
Connection of a red-green signaller. Select the value 0 in
menu item 45 and the value 1 in menu item 46.
b
Fig.
Example: pre-warning time / acoustic signal
c
Fig.
Connection for the mutual locking of 2 doors (lock circuit).
Select the value 2 or 3 in menu item 50 and the value 0 in menu
item 45.
d
Fig.
Connection for the mutual locking of 3 doors (lock circuit).
Select the value 2 or 3 in menu item 50 and the value 0 in menu
items 45 and 46.
T100 R-FU 1,5kW