Menu 7 FU settings
Settings for door operation (menu item 70-79)
The associated parameters such as maximum motor speed and
the optimum door operation profile are saved for each motor type.
Do not modify default settings
NOTICE
Adjusting the default settings is not required and
may cause faults.
Crush hazard and risk of being struck by the
CAUTION
closing door if approach area monitoring is
insufficient!
If the closing speed exceeds 50 cm/s, the move-
ment area on both sides of the door needs be
monitored over the entire door width and to a
depth of 90 cm.
Menu point 78 Selecting the brake (frequency converter)
Crush hazard and risk of being struck by
WARNING
falling door
Select the correct brake type before commission-
ing.
Incorrect adjustment of the brake type can cause
the door to fall.
Adjust the motor brake according to the type of motor installed
and as follows:
Brake type A, brake operating without power supply
– (Value 0) Brake is applied simultaneously when starting
the motor.
– (Value 1-9) Applying the brake is delayed after starting
the motor.
Brake type B, brake opening without power supply
– (Value 10) Brake is opened simultaneously when starting
the motor.
– (Value 11-19) Opening the brake is delayed after starting
the motor.
Menu point 79 Selecting the drive (frequency converter)
Select the drive in accordance with the specifications given in the
Program overview chapter in menu item 79.
NOTICE
Damages to the drive, control or door due to
the use of external drives
The control unit may only be operated with a
drive contained in the program overview. The
use of external drives can result in damages of
drive, control unit or door.
Test run
When programming has been completed, carry out a test run by
executing all operating functions. When all operating functions
have been executed correctly, the connected door system is
ready for operation.
28 - EN
6

Program overview

Menu 3 Basic settings
Menu
Entry
Selection
item
30
Door setting of upper end position
Reversal of the direction (press for 5 s)
31
Door setting of lower end position
32
Door setting for 1/2 opening position
33
Fine correction of upper end position
50
Factory settings
50 - 0
0...80 mm lower
50 - 99 0...80 mm higher
34
Fine correction of lower end position
50
Factory settings
50 - 0
0...80 mm lower
50 - 99 0...80 mm higher
35
Selection of closing edge safety device
Measurement display (press 5 seconds)
0
Optical closing edge safety device OSE
1
Electrical safety edge 8K2 (default setting)
2
Pressure wave switch with testing
3
Electrical safety edge 8K2 with slack rope
switch
36
Selection of photoelectric sensor
0
Without photoelectric sensor (default setting)
1
2-wire photoelectric sensor LS2
2
4-wire photoelectric sensor LS5 photoelectric
reflection sensor
3
Photoelectric sensor LS2, mounted in frame
4
Photoelectric sensor LS5 photoelectric reflec-
tion sensor mounted in frame
5
Light grid with testing (SG14)
37
Correction of pre-limit switch closing edge safety
25
Correction of pre-limit switch closing edge
safety (default setting)
25 - 0
0...50 mm lower
25 - 99 0...100 mm higher
38
Response of photoelectric sensor
0
No reduced open time (default setting)
1
Reduced open time with AR operation
- -
Exit menu
Menu 4 Further door settings
Menu
Entry
Selection
item
40
Selection of operating mode
0
Dead man OPEN / dead man CLOSE
1
Pulse OPEN / dead man CLOSE
2
Pulse OPEN / pulse CLOSE (default setting)
3
AR - automatic closing
41
Response to closing edge safety device
0
Full reversing (default setting)
1
Partial reversing
T100 R-FU 1,5kW