Herunterladen Inhalt Inhalt Diese Seite drucken

Connection Of Mains/Charger Unit 013970, 12 V Dc / 18 Ah; Start-Up Procedure; Preparation; Electrical Start-Up - Honeywell AXS4Secure Montage, Anschluss, Anleitung

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Mounting and Connection Instructions AXS4Secure
10.5

Connection of mains/charger unit 013970, 12 V DC / 18 Ah

Computer/Connection PCB
AXS4Secure
11.

Start-up procedure

11.1

Preparation

All system components must have been properly installed. Measure all lines from the connection to the
control panel in order to detect any line interruptions or short circuits. Ensure that there is no earth
fault.
Cover contacts of system components and the control panel must be closed.
Cover contacts of the control panel, possibly using a shorting bar, or keep closed using a magnet.
11.2

Electrical start-up

*
Disconnect the computer/connection PCB from the mains/charger unit.
*
Switch on the mains/charger unit.
*
Measure the battery charging voltage at the battery connection cable (nominal value +13.8V DC).
(Please note the Mounting and Connection Instructions of the Mains/charger unit.)
*
Connect the battery (observe polarity!).
*
Reconnect the mains/charger unit to the connection PCB.
*
The control panel goes through its boot procedure. The four "Status
information" LEDs light statically for around 30 seconds.
The green LED5 indicates successful termination of the boot and initializa-
tion process:
- Blinking slow -> Not programmed
- Blinking fast
-> No or invalid license
- Steady on
-> Operation/initialization successful
Fault
Connection to
+12 V DC
power supply unit
0 V
Mains
Cable entry
PE from mains cable
The Mounting and Connection Instruction of the mains/charger unit is enclosed.
Mains 110 V AC / 230 V AC
PE connector for
power supply
L
PE
N
PE
+
black
Battery
Connection strip
for shield and PE
LED indication on the power supply:
- LED1 red
PE
- LED2 green
F1 Mains
T2A HRC
F1
F2
S
+
F2 12 V DC
-
T1.6A
N
red
F3 Battery
+
F1.6A
F3
LED
LED
red
green
Fault
Mains present
Ethernet
LEDs Status information
LED4 5 6 7