7.3

Controller interfaces

7.3.1

Operating mode

With the jumpers Port1 – 4 the operating mode of the interfaces (RS-485 or BUS-2) is selected.
For this application, the RS-485 mode must be selected (see below "Set jumpers").
7.3.2

End-of-line resistors

With the jumpers R
1 – 4 the end-of-line resistors of the 4 RS-485 interfaces are aktivated or deakti-
A
vated (see below "Set jumpers").
Basic rule: The bus line must be terminated at both ends with 120 Ohm.
Example 1: The EOL resistor can be attached directly on the reader (e.g. Insertic readers)
AXS4
Secure
R120
B
A
Example 2: The EOL resistor can not be attached directly to the reader (e.g. Accentic readers)
AXS4
Secure
R120
B
A
Set jumpers:
Controller 3
B (D-)
RS-485
A (D+)
Port3
R 3
A
Controller 4
B (D-)
RS-485
A (D+)
Port4
R 4
A
max. 2000 m
max. 2000 m
Controller 1
B (D-)
RS-485
A (D+)
R 1
A
Port1
Controller 2
B (D-)
RS-485
A (D+)
R 2
A
Port2
Reader
RS-485
R120
A
Reader
RS-485
A
Distributor
R120
max. 5 m
Operating mode Controller 1-4:
1
1-2 set
2
3-2 set
3
Port1 – 4
End-of-line resistor RS-485 Bus 1-4:
both set
both not set
R 1 – 4
A
31
B
B
not allowed
RS-485
aktive
not aktive