AC Output (On-grid)
X3-HYB-
Model
4.0-P
Norminal AC
power [VA]
Max. apparent AC
power [VA]
Rated grid voltage
(AC voltage range)
[V]
Rated grid
Frequency [Hz]
Norminal AC
current [A]@230V
Max. AC current
[A]@220V
Current (inrush)
Max. output fault
current
Max. output
overcurrent
protection
Displacement
power factor
Total harmonic
distortion (THDi,
rated power)
Parallel operation
Load control
X3-HYB-
5.0-P
5000
4000
(4999 for
AS 4777)
5500
4400
(4999 for
AS 4777 )
5.8
7.2
6.7
8.4
~1 (Adjustable from 0.8 leading to 0.8 lagging)
X3-HYB-
X3-HYB-
6.0-P
8.0-P
6000
8000
6600
8800
400V/380
50/60
8.7
11.6
10.0
13.4
115 a.c.A (rms)
85 a.c.A (peak)
88 a.c.A (peak)
<3%
Yes
Yes
X3-HYB-
X3-HYB-
10.0-P
12.0-P
10000
(9999 for
12000
AS 4777 )
11000
(9999 for
13200
AS 4777 )
14.5
17.5
16.7
20.0
X3-HYB-
15.0-P
15000 (
14999 for
AS 4777)
16500 (
14999 for
AS 4777)
21.8
25.0
87