Crawl Path Optimization
Speed V
E
Ogive Function
a) LF.75 = 0
off
8. Parameter Description
Unit:
Value range:
Factory Setting:
The levelling position can be exactly adjusted with the crawl path
optimization. Condition: the stop switches in all floors have the same
distances to the levelling position for both directions. The crawl
speed (LF.41) and stopping jerk (LF.54) must be adjusted before the
path optimization crawl speed.
V
V
N
V
E
Unit:
Value range:
Factory setting:
When the ogive function is switched off the acceleration is immediately
interrupted at the delay point.
V
LF.75 = 0
V
N
V
E
millimeter
0...300 mm
0.0 mm
LF.74
LF.74
stop switcha
1
0 = off
1 = speed controlled
2 = time controlled
0
delay point
ANTRIEBSTECHNIK