Start-up
5.3
Adaption run
Once the batteries have been inserted, the motor
reserves the valve pin.
After the valve pins has been reversed completely (motor
no longer moves), the radiator thermostat can be moved
(see figure 6). An adaption run has to be performed in
order to adapt the device to the valve. To do this, please
proceed as follows:
To start the adaption run, close the battery com-
partment (E) using the square key (see figure 2+3).
The adaption run is alternatively started 3 minutes
after reaching the valve pin end position.
Now, the radiator thermostat performs the adapting run.
After the adaption run, installation is completed and the
device can be individually configured and controlled.
If the adaption run was initiated prior to installation
or if it could not be fully performed, the device LED
(C) lights up red up to 10 times at intervals of 10
seconds. If the audible signalling device is activat-
ed, it sounds parallel to the LED. By turning the bat-
tery compartment lock (F) using the square key
(see figure 2), the motor moves back to the valve
pin end position.