Operation
Other settings
10 Select the target of External Input Control. (All Groups/Block/Group).
Tap the button of a Group to switch its selection state.
Tap the button of a Block to switch the selection state of all the Groups in the Block.
Tap the "All Groups selection" button to switch the selection state of all the Groups.
The selected groups are indicated with a check mark.
11 Tap "Setting completed" to confirm the set contents and return to the External Input/Output Setting screen .
5.4.4.5 External Output Setting
1 Select "External Input/Output Setting" on the Service Menu screen.
Selection is not possible when air conditioners are in operation, or when the contact for external input signal is ON.
2 Select the Output target of the External Output (Output 1, Output 2).
3 Select the function to be used with the external output.
The button for the selected function is highlighted in yellow.
4 Tap "Service Menu" to complete the external Input/Output Setting and return to Service Menu screen.
(3)
74
PMML0332A rev.0 - 05/2015
(10)