Installation
3.3 DESCRIPTION OF THE PARTS
Colour LCD with touchscreen
For operation and monitoring of the units through the touchscreen display. It
is operated by using the touch pen (accessory). The touchscreen display will
be automatically turned off when the touchscreen is not operated for a given
length of time.
Gesture controls such as multi touch (simultaneous press of several points
of the screen) or swipe operation are not supported.
Tap 2 places simultaneously
Flick Operation
Touch Pen
Use the touch pen to operate the touchscreen of the central station
Operation Indicator
Indicates the Run/Stop state of the units
OFF:
All the units are stopped.
ON (Green):
One or more units are in operation.
Flashing (Red): In abnormal condition.
Power Indicator
Indicates the power state of the central station.
OFF (lamp): Power is turned OFF
ON (lamp): Power is turned ON
Hole for attachment of the touch pen holder (accessory).
Attaching holes are located on both sides.
Attach the touch pen holder to one side.
TB2
Terminals for connection of the H-LINK control wiring
CN1 ~ CN3
Terminals for connection of connector cords (accessory) in case of using
external input/output
TB1
Terminals for connection of the power cable
Power switch to turn OFF the power supply
Use this switch to prevent electrical shock when the case of the unit is
opened.
Fuse for H-LINK Transmission Line
H-LINK Transmission Line (Behind the PCB). For protection of H-LINK
transmission line.
DSW2
For terminating resistance. It is used for transmission line recovery.
Rotary Switch for Address Setting
For address setting of controller
DSW1
For optional function setting
?
N O T E
Remove the protection sheet on the LCD (liquid crystal display) before using this product.
!
D A N G E R
DO NOT remove the covers of parts marked with "
may cause a serious electrical shock.
4
PMML0332A rev.0 - 05/2015
Right side
" for safety. If these covers are removed, contact with the inside components
Front side
Rear side
When unit body is open
HIGH VOLTAGE
高電圧注意