Herunterladen Diese Seite drucken

Hitachi CENTRAL STATION PSC-A32MN Installations- Und Betriebshandbuch Seite 78

Vorschau ausblenden Andere Handbücher für CENTRAL STATION PSC-A32MN:

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 181
Operation
5.4.4 External Input/Output Setting
The External Input/Output function of the central station provides the capacity to control 4 inputs and 2 outputs.
Select "External Input/Output Setting" on the "Optional Function Setting" screen to access the setting menu.
Input and Output
Input 1
Input 2
Input 3
Input 4
Output 1
Output 2
5.4.4.1 External Input Function
1 All Run/Stop (Level)
Performs run/stop operation of all groups simultaneously by means of the external input signal.
2 All Run (Pulse)
Performs run operation of all groups simultaneously by means of the external input signal.
3 All Stop (Pulse)
Performs stop operation of all groups by means of the external pulse signal input.
4 Emergency Stop (Level)
The operation of all groups is stopped simultaneously by means of the external emergency stop signal.
While "Emergency Stop" is being carried out, "Central Control" is displayed in the LCD of the remote control switch, and
operation from the remote control switch becomes disabled.
In case of using other central stations together, "Run/Stop" operation is available from the other central stations even during the
emergency stop.
5 Demand Control Function
The external demand control signal allows to cut a peak demand of electrical consumption. The external demand signal can only be
input through input terminal 1. The operation mode of the selected group is changed by the demand signal as shown below.
Stop (*2)
Indoor Unit Operation Stop with RCS Operation Prohibited Mode
Run Mode Shift (*2) (*4)
Operation Unit Capacity
Control the value of outdoor unit capacity in the setting value.
Control (*5) (*6) (*7)
(*1): Do not set "OFF" or "Run Mode Shift" when using other central stations at the same time. When setting outdoor unit capacity control, set one of
the central station and do not set the others.
(*2): Setting is only possible for Stop or Run Mode Shift. And it is not possible to set multiple contact points.
(*3): When operating in "AUTO" mode, or when "Fixing Operation Mode" is enabled at "Optional Function Setting".
(*4): Operation stops even if it is in Auto mode, or if the operation mode is fixed in the optional function settings.
(*5): Outdoor unit capacity control can be set to multiple contact points. When there is a signal input in multiple contact points, the priority for the
execution of the controls is established according to the input number (Input 1 > Input 2 > Input 3 > Input 4).
(*6): There are cases in which the outdoor unit may not support certain settings, or in which available settings may differ according to its capacity
value. Please contact with your dealer or with the designated customer service centre for detailed information.
(*7): It is possible to control via schedule without using demand control.
70
PMML0332A rev.0 - 05/2015
Connection
All Run/Stop (Level)
CN1 Pins 1-2
Emergency Stop (Level)
CN1 Pins 2-3
All Run (Pulse)
CN2 Pins 1-2
Demand (Shift of Run/Stop mode / Outdoor Unit Capacity Control)
All Stop (Pulse)
CN2 Pins 2-3
No Setting (Factory Setting)
All Run
CN3 Pins 1-2
No Setting (Factory Setting)
CN3 Pins 1-3
All Alarm
Demand Signal ON
COOL or DRY switch to FAN
(Remote Control Operation Prohibited)
HEAT switch to STOP
(Remote Control Operation Prohibited)
(Setting Value: 100/90/80/70/60/50/40/0%)
Function
Demand Signal OFF
The operation condition returns to the previous
state. (*3)
Cancel the capacity control.

Werbung

loading