BNI PNT-508-105-Z067 / BNI PNT-508-105-Z077 / BNI PNT-502-102-Z078
Network interface
2
System integration (continued)
Assigning the device name
► Assign the desired device name and assign it to the
selected, found device by clicking on a
The device name must match the name that
was previously configured (see chapter Setting
the device name and PROFINET address).
Fig. 2-15: Assigning the device name
Completing the configuration
► Download the configuration into the module
parameterization.
⇒ The bus error should be reset at the module.
If the module continues to report a bus error, this could be
because the device relationship has not been established.
The following remedies are possible:
► Via t
> e
arget SyStem
thernet
b
, scan the network and check whether the
rOwSe
device is reporting under the correct device name and
IP address.
► If necessary, change the IP address or the device
name.
► Assign the device name to the device again and
download the configuration.
14
english
.
SSign name
> e
>
thernet SubScriber
2.2
Functions in the module parameters
Module settings
Function
Description
Global diagnosis
With this function, all diagnosis
messages of the device can be
suppressed or permitted (optical
diagnosis signals and diagnosis in
configured diagnosis modules are
not affected).
Undervoltage of the
With this function, the diagnosis
sensor supply
message Undervoltage in module
sensor supply is permitted or
suppressed (optical diagnosis
signals and diagnosis in
configured diagnosis modules are
not affected).
Undervoltage of the
With this function, the diagnosis
actuator supply
message Undervoltage in the
module actuator supply is
permitted or suppressed (optical
diagnosis signals and diagnosis in
configured diagnosis modules are
not affected).
Sensor short circuit
With this function, the diagnosis
to output
message Sensor short circuit to
module output is permitted or
suppressed (optical diagnosis
signals and diagnosis in
configured diagnosis modules are
not affected). The function only
applies to channels or pins that
are configured as outputs.
Channels or pins that are
configured as inputs are not
affected.
Tab. 2-2:
Module settings