Network interface
2
System integration (continued)
Device replacement without exchangeable medium
The modules also support simple device replacement in
LLDP mode (Link Layer Discovery Protocol).
Activating device replacement without exchangeable
medium
► In the CPU hardware configuration, activate the
S
uppOrt device replacement withOut exchangeable medium
checkbox.
Fig. 2-6:
Support device replacement without exchangeable
medium
► Create the ProfiNet topology in the hardware
configuration.
The connections of the individual ports must
match the hardware wiring. If the topology in the
hardware configuration is not a match, errors
can occur.
Fig. 2-7:
Device replacement without exchangeable medium:
Topology