Connection
XDI Digital inputs
2
5
1
2
X12
X13
X205
The wire size accepted by all screw connectors (for both stranded and solid wire) is
2
0.5 ... 2.5 mm
(24...12 AWG). The torque is 0.5 N·m (5 lbf·in).
Start-up the drive
Before you start up the drive, make sure that the installation is completed.
Make sure also that it is safe to start the motor. Disconnect the motor from
other machinery if there is a risk of damage or injury.
Before you activate the automatic fault reset or automatic restart functions
of the drive control program, make sure that no dangerous situations can
occur. These functions reset the drive automatically and continue operation
after a fault or supply break. If these functions are activated, the installation
must be clearly marked as defined in IEC/EN/UL 61800-5-1, subclause 6.5.3,
for example, "THIS MACHINE STARTS AUTOMATICALLY".
Use the control panel to do the start-up procedure. The two commands at the bottom
of the display show the functions of the two softkeys
display. The commands assigned to the softkeys are different depending on the
context. Use the arrow keys
depending on the active view. Key
Term
DI1
+24VD
DI2
DIOGND
DI3
1
DI1
DI4
2
DI2
DI5
3
DI3
DI6
4
DI4
5
DI5
6
DI6
OUT
OUT
SGND
SGND
3
IN1
IN1
4
IN2
IN2
Safety options connection
Control panel connection
Memory unit connection
,
,
and
?
shows a context-sensitive help page.
EN – Quick installation instructions 15
Description
Stop (0) / Start (1)
Forward (0) / Reverse (1)
Reset
Acc/Dec time select
Constant speed 1 (1 = On)
By default, not in use.
Safe torque off circuits must be closed for the
drive to start.
and
located below the
to move the cursor or change values
EN