DESIGN

Type BHK 052 OPSO/UPSO
a
Type BHK 052B
Inlet connection
Outlet connection
Safety Over-Pressure Shut Off valve
OPSO / UPSO
Safety Pressure Shut Off valve
a
OPSO
Low pressure regulator with integrated
pressure relief valve PRV
If used in buildings, a ventilation line must be installed from the breather of the
product to outdoors!

ADVANTAGES AND EQUIPMENT

Insect protection option
Check regularly that the sieve is not blocked. A blocked sieve can increase or
lower the outlet pressure and cause the safety overpressure shut-off valve OPSO resp.
UPSO to respond. Clean or replace it as required.
Emergency supply connector option
In case of unforeseen events, such as the gas tank becoming empty, the gas supply can be
maintained until the gas tank is refilled with the help of a gas cylinder and the emergency
supply set. With the emergency supply set (Part No. 02 498 00) connect a gas cylinder to the
emergency supply connector (G 3/8 LH-KN) of the pressure regulator.
The gas cylinder is not intended for permanent supply. It is intended only as a
temporary solution until the gas tank has been refilled.
Artikel-Nr. 05 288 50 m
a
a
Insert in the breather on the 8 mm vent socket or screw into the female
thread G 1/8.
Behälterregler-Kombination PS 25 bar
a
a
Breather PRV, Insect protection device
Emergency supply connector
Test connector
Breather, Insect protection device
Regulator support, adjustable
Protection cap/Visual indicator for OPSO,
Protection cap/Visual indicator for
OPSO / UPSO
(see page 27)
Type BHK 052
a
a
Type BHK/K
a