5
34
DANGER
Safety instructions
Danger!
Water temperatures above 45 °C lead to severe scalding of the skin!
▪
Do not stay in rooms where thermal disinfection is in progress.
▪
The operator must ensure that access to rooms with running thermal fl ushing is prohibited.
▪
When starting up a thermostat battery, check the maximum mixed water temperature at the safety stop of the temperature hand-
le, due to any deviating desired temperatures.
▪
Factory setting: TWM = 40°C
▪
For time-shower variants without thermostat, the maximum temperature (max. 45°C) for centrally fed mixed water must be
observed.
▪
When commissioning or replacing (hot) water- carrying components, it must be ensured that only authorised personnel have
access to the components concerned.
▪
The worksheet DVGW W551 must be observed.
▪
Hazardous areas must be labelled in accordance with EN ISO 7010 and DIN 4844-2.
!
Danger!
Contact voltages of more than 50 V/AC and 120 V/DC lead to severe health consequences and can cause
death.
▪
Electrical wiring may only be carried out by a qualifi ed electrician in accordance with DIN VDE 105-100.
!
Danger!
Contaminated drinking water can cause diseases that can be fatal.
▪
In case of contamination, the pipes and components must be fl ushed for 3 minutes at a temperature >70°C according to works-
heet DVGW W551.
▪
Discharge hot water in a controlled fl ow.
▪
Before use, ensure that all parts of the system are suitable for carrying out the measure.
Danger!
Improper installation / assembly of showerheads, substructures/supporting elements may result in falling
components, resulting in serious injuries to the head and body.
▪
Installations and assembly work must always be carried out by a qualifi ed specialist.
▪
Check the wall condition for suitability for installa tion by means of the supplied fasteners.
▪
If necessary, different screws and dowels may be required.
▪
It is essential that shower heads are fastened to the device provided for this purpose in accordance with the installation instructions.
▪
Check the fi xation frequently.
CONTI Sanitärarmaturen GmbH | Hauptstraße 98 | 35435 Wettenberg | Deutschland | Tel. +49 641 98221 0 | Fax +49 641 98221 50 | info@conti.plus
CONTI Sanitärarmaturen GmbH | Hauptstraße 98 | 35435 Wettenberg | Deutschland | Tel. +49 641 98221 0 | Fax +49 641 98221 50 | info@conti.plus
www.conti.plus | Druckfehler und Irrtümer sowie technische und maßliche Änderungen vorbehalten. | Errors and technical changes remain reserved.
www.conti.plus | Druckfehler und Irrtümer sowie technische und maßliche Änderungen vorbehalten. | Errors and technical changes remain reserved.
scalding
electric shock
contamination
Inadequate fastening