Herunterladen Inhalt Inhalt Diese Seite drucken
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 29
4. Power wiring
WTC-LEX/-BEX power voltage
Model
Voltage
WTC-LEX-WD
100-240 VAC/DC; -15%/+10%;
WTC-LEX-ST
50/60 Hz;
Only to power light outputs.
The module is powered via the
subnetwork.
Overvoltage Category II - 2.5 kV
WTC-BEX-WDLV
100-240 VAC; -15%/+10%;
WTC-BEX-STLV
50/60 Hz; Overvoltage Category II
- 2.5 kV
WTC-LEX/-BEX power voltage
Model
Typical
Consumption
WTC-LEX-WD
0.3 W + all
WTC-LEX-ST
external loads
WTC-BEX-WDLV
< 1 W + all
WTC-BEX-STLV
external loads
WTC-LEX/-BEX protections
Model
Protection
WTC-LEX-WD
6.0 A external circuit breaker
WTC-LEX-ST
type C (250 VAC min)
WTC-BEX-WDLV
2.0 A external circuit breaker
WTC-BEX-STLV
type C or 2.0 A fast acting high
breaking external fuse
(250 VAC min)
Use an external circuit breaker on the mains,
as specified in the table above and shown in
the figure below to protect the expansion
module against power line spikes. The
protection device must remain close to the
protected device.
External Circuit Breaker
Figure 7: Power wiring
IMPORTANT: The wires section must remain
between 1 mm² and 1.5 mm². Make sure the cable
performances suit the connected loads.
6
5. Input wiring
Each expansion module has physical
connections for four inputs (marked as DIx
for Digital Inputs). All input wiring must be
connected using the provided detachable
connectors.
Wiring digital inputs (DIx)
The input configuration is used to monitor
digital dry contacts.
Digital Dry Contact
Max.
Figure 8: Digital input – dry contact (NO-NC) -
consumption
Reserved for future use
6.0 A

6. Output wiring

1.2 A
Depending on models, the WTC-LEX/-BEX
expansion modules have physical
connections for ON/OFF light outputs,
dimming light outputs and 24 VDC shade /
sunblind outputs.
All output wiring must be connected using
the specified detachable connectors.
Before connecting any output equipment to
the expansion module, refer to the
installation guide of the equipment
manufacturer. Make sure the cable
performances suit the connected loads.
Expansion module
WTC-LEX-WD
WTC-LEX-ST
WTC-BEX-WDLV
WTC-BEX-STLV
NO-NC
Outputs type
On/Off Lighting or
1-10 V Dimming
Lighting
24 VDC Shade /
Sunblind
Outputs
4
4

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Wtc-lex-stWtc-bex-wdlvWtc-bex-stlv

Inhaltsverzeichnis