Description
Adjustable parameters
Auto bypass
[enabled], [disabled]
"enabled" means UPS will have
bypass output when utility power on.
"disabled" means UPS will not have
bypass output when power on but
could get bypass output when UPS is
fault or overload.
Start without
[enabled], [disabled]
battery
Setting "active" means: the UPS can
be started without an inserted battery
system.
Clear
The number after "Total events" shows
Event
how many events are currently stored
Log
in the log.
Press the "ENTER" button for one
second to reset the event count to
zero and clear the log.
LCD Contrast
[-5], [-4], ...[-1], [0], [+1], ...[+4], [+5]
Restore Factory
[no], [yes]
Settings
Setting only available in
UPS stand-by mode.
Restoring the factory settings:
returns all user-configurable
EEPROM settings to default
factory settings
resets all pending on/o
commands
Clears the Event Log and resets all
time stamps
Resets the battery test status
Initiates the Self Diagnostics test
The restore Factory Settings process is completed after the UPS was switched o
completely. Wait until the fans stopped to allow the UPS internal EEPROM overwriting.
Presetting
enabled
disabled
0
no