Nominal frequency
Synchronization range
Synchronization speed
Power factor range
Inverter frequency
Sinus waveform
Connection
Crest factor
Overload behaviour
Overload bypass
Short circuit
Battery
Autonomy Time
External
battery module
With integrated battery
1 add. battery module
2 add. battery modules
Battery check
(programmable)
Rated DC voltage (intermediate circuit)
Protect C 1000
Protect C 2000
50 Hz / 60 Hz ±0.2 Hz
(Tolerance in battery mode or free running
in variable-frequency inverter mode)
50 Hz / 60 Hz ±10 %
1 Hz/s
0.3 lag. to 0.9 cap.
at full output
Power reduction of 20 % to 0.5 cap.
40 % power reduction
(Bypass disabled, Input Frequency Range
40 - 70 Hz)
Sinus waveform distortion
<3 % THD (linear load)
<5 % THD (non-linear load)
IEC sockets
3:1
up to 105 % continuous;
>105 % – <110 % for 60 s;
110 % – <125 % for 30 s;
125 % – 150 % for 10 s;
Then automatic inverter to Bypass
in < 4 ms (switches back when
overload damps = Load < 90%)
Up to 125 % continuous
>125 % – 150 % 10 min.
3 x I N for 100 ms
cosφ = 0.8 lag. / 100 % charged battery
C 1000 C 2000 C 3000
4.5 min. 7 min. 3.5 min.
25 min. 38,5 min. 21 min.
51 min. 70 min. 45 min.
daily; weekly; monthly
36 VDC
96 VDC