2.3 TECHNICAL INFORMATION

Power rating (PF 0.9 for 0 – 35°C)
Protect C 1000
Protect C 2000
Protect C 3000
Power rating (PF 0.8 for 35 – 45°C)
Protect C 1000
Protect C 2000
Protect C 3000
UPS Input
Rated input voltage
Rectifier voltage range
(without battery
operation, 100 % load,
cosφ = 0.8 lag.)
Rectifier voltage range
(without battery operation,
50 % load, cosφ = 0.8 lag.)
Nominal frequency
Frequency tolerance
Power consumption at PF0.9 full load (max.)
Protect C 1000
Protect C 2000
Protect C 3000
Bypass voltage range
Mains feedback factor
Connection
UPS Output
Rated output voltage
1000 VA (cos φ = 0.9 lag.) 900 W
2000 VA (cos φ = 0.9 lag.) 1800 W
3000 VA (cos φ = 0.9 lag.) 2700 W
1000 VA (cos φ = 0.8 lag.) 800 W
2000 VA (cos φ = 0.8 lag.) 1600 W
3000 VA (cos φ = 0.8 lag.) 2400 W
1ph~ / N / PE
200 / 208 / 220 / 230 / 240 VAC
176 – 300 VAC
110 – 300 VAC
50 Hz / 60 Hz
(autom. detection or manual)
±10 %
5.4 / 5.2 / 5.0 A
U
= 220 / 230 / 240 VAC
N
10.0 / 9.6 / 9.2 A
U
= 220 / 230 / 240 VAC
N
14.7 / 14.1 / 13.5 A
U
= 220 / 230 / 240 VAC
N
176 VAC – 264 VAC
0.99 (THDi <5 %)
IEC connector
200 / 208 / 220 / 230 / 240 VAC ±2 %
Power reduction at 200 VAC 20 % /
at 208 VAC 10 %
EN