Alarm or Notice
Possible cause
Output Overload
The load level is at
(Alarm #25)
or has exceeded the
Intermittent Alarm
configurable threshold
limit for a Overload
condition.
Battery DC Over
The battery voltage
Voltage
level has exceeded the
(Alarm #68)
maximum allowable
Intermittent Alarm
limits.
Charger Failure
A battery charger fault
(Alarm #34)
has been detected.
Continuous Alarm
Output Short Circuit
The uninterruptible
(Alarm #58)
power supply has
Intermittent Alarm
detected abnormal
low impedance that
placed on its output
and considers it a short
circuit.
Heat sink Over
The uninterruptible
Temperature
power supply has
(Alarm #73)
detected that one of its
Intermittent Alarm
heat sinks has exceeded
the maximum defined
operating temperature.
Possible fan failure
see below .
Remark / Action
The UPS can support
the load indefinitely at
this load level.
The alarm clears when
the load drops below
5% of the set point.
The uninterruptible
power supply turns o
the charger until the
next power recycle.
Contact your service
representative.
The UPS turns o the
charger until the next
power recycle. Contact
your service
representative.
The uninterruptible
power supply operates as
a constant-current
source (3 x I
) and
N
shuts down after five
cycles 100ms .
Make sure that the fans
are spinning and that
the air intake vents on
the uninterruptible
power supply are not
blocked. After the
maximum temperature
is reached, the
uninterruptible power
supply shuts down.