Protect C 3000
Battery charging current
(max.)
Battery type
Recharge time (to 90 %
of rated capacity)
Communication
Interfaces
Remote shutdown contact
Shutdown Software
General data
Classification
ull load e icienc
(AC-AC / DC-AC)
ull load e icienc
(ECO / Transfer time
<10 ms) (economical
mode)
Inherent noise
(1 m distance)
Type of cooling
Operating temperature
96 VDC
1 ADC
sealed maintenance free (VRLA)
Protect C 1000
12 V 7 Ah x 3
Protect C 2000
12 V 7 Ah x 8
Protect C 3000
12 V 7 Ah x 8
Protect C 1000 BP
12 V 7 Ah x 3 x 2
Protect C 2030 BP
12 V 7 Ah x 8 x 2
~ 8 h (UPS with internal battery)
~ 24 h (with 1 additional battery)
~ 40 h (with 2 additional batteries)
RS232 SUB-D (9-pin), USB
Additional: communication slot for
Extensions (eg, relay card, SNMP (Pro), ...)
Potential-free (optionally programmable as
opener or closer)
"CompuWatch"
popular operating systems like:. Windbows,
Linux, Mac, Unix, Novell, Sun
VFI SS 111 acc. to. IEC 62040–3
double conversion technology (INV / BATT)
VFI SS 311 acc. to IEC 62040–3
ECO mode
Protect C 1000
Protect C 2000
Protect C 3000
Protect C 1000
Protect C 2000
Protect C 3000
Protect C 1000
Protect C 2000
Protect C 3000
Forced cooling by variable speed fans
0 °C to 45 °C Recommendation +15 °C
to +25 °C (due to battery system)
for all
87 % /
85 %
88 % /
85 %
88 % /
85 %
94 %
94 %
94 %
44 dB (A)
49 dB (A)
49 dB (A)