INSTALLATION MANUAL
10
Minimum floor area(for R32)
- The appliance shall be installed, operated and stored in a room with a floor area larger than the
minimum area.
- Use the graph of table to determine the minimum area.
- Console model(For EU market) should be installed only in accordance with IEC 60335-2-40:2018
Edition 6.0.
IEC 60335-2-40:2013+A1:2016 Edition 5.1
Amin (m
2
)
600
500
400
300
200
100
0
0
1.224
2
3
4
- m : Total refrigerant amount in the system
- Total refrigerant amount : factory refrigerant charge + additional refrigerant amount
- Amin : minimum area for installation
IEC 60335-2-40:2013+A1:
IEC 60335-2-40:
2016 Edition 5.1
2018 Edition 6.0
Floor standing
Floor standing
2
m (kg)
Amin (m
)
m (kg)
Amin (m
< 1.224
-
< 1.842
1.224
12.9
1.842
1.4
16.82
2.0
1.6
21.97
2.2
1.8
27.80
2.4
2.0
34.32
2.6
2.2
41.53
2.8
2.4
49.42
3.0
2.6
58.00
3.2
2.8
67.27
3.4
3.0
77.22
3.6
110.30
3.2
87.86
3.8
122.90
3.4
99.19
4.0
136.17
3.6
111.20
4.2
150.13
3.8
123.90
4.4
164.77
4.0
137.29
4.6
180.09
4.2
151.36
4.8
196.09
4.4
166.12
5.0
212.77
4.6
181.56
5.2
230.13
4.8
197.70
5.4
248.18
5.0
214.51
5.6
266.90
5.2
232.02
5.8
286.30
5.4
250.21
6.0
306.39
5.6
269.09
5.8
288.65
6.0
308.90
Amin (m
2500
2000
1500
1000
500
m (kg)
0
0
5
6
7
8
IEC 60335-2-40:2013+A1:
IEC 60335-2-40:
2016 Edition 5.1
2018 Edition 6.0
Wall mounted
2
2
)
m (kg)
Amin (m
)
m (kg)
-
< 1.224
-
< 1.842
28.88
1.224
1.43
1.842
34.04
1.4
1.87
41.19
1.6
2.44
49.02
1.8
3.09
57.53
2.0
3.81
66.72
2.2
4.61
76.60
2.4
5.49
87.15
2.6
6.44
98.39
2.8
7.47
3.0
8.58
3.2
9.76
3.4
11.02
3.6
12.36
3.8
13.77
4.0
15.25
4.2
16.82
4.4
18.46
4.6
20.17
4.8
21.97
5.0
23.83
5.2
25.78
5.4
27.80
5.6
29.90
5.8
32.07
6.0
34.32
IEC 60335-2-40:2018 Edition 6.0
2
)
2
4
6
8
10
12
IEC 60335-2-40:2013+A1:
2016 Edition 5.1
Wall mounted
Ceiling Mounted
2
Amin (m
)
m (kg)
Amin (m
-
< 1.224
-
4.44
1.224
0.956
2.0
4.83
1.4
1.25
2.2
5.31
1.6
1.63
2.4
5.79
1.8
2.07
2.6
6.39
2.0
2.55
2.8
7.41
2.2
3.09
3.0
8.51
2.4
3.68
3.2
9.68
2.6
4.31
3.4
10.93
2.8
5.00
3.6
12.26
3.0
5.74
3.8
13.66
3.2
6.54
4.0
15.13
3.4
7.38
4.2
16.68
3.6
8.27
4.4
18.31
3.8
9.22
4.6
20.01
4.0
10.21
4.8
21.79
4.2
11.26
5.0
23.64
4.4
12.36
5.2
25.57
4.6
13.50
5.4
27.58
4.8
14.70
5.6
29.66
5.0
15.96
5.8
31.81
5.2
17.26
6.0
34.04
5.4
18.61
5.6
20.01
5.8
21.47
6.0
22.98
Floor standing
Wall mounted
Ceiling mounted
m (kg)
14
16
IEC 60335-2-40:
2018 Edition 6.0
Ceiling Mounted
2
2
)
m (kg)
Amin (m
)
< 1.842
-
1.842
3.64
2.0
3.95
2.2
4.34
2.4
4.74
2.6
5.13
2.8
5.53
3.0
5.92
3.2
6.48
3.4
7.32
3.6
8.20
3.8
9.14
4.0
10.13
4.2
11.17
4.4
12.26
4.6
13.40
4.8
14.59
5.0
15.83
5.2
17.12
5.4
18.46
5.6
19.85
5.8
21.30
6.0
22.79