The alarm conditions described below
are those that can be detected by the
controller, and are indicated to the user
by way of a warning message in the
display.
Temperature probe alarm
EN
The probe measures the temperature of
the water in the tub or pool and allows
the control system to keep it at the set
point value entered from the keypad.
The range of permissible water
temperature values is from 5 to 45 °C;
any values outside of this range are
considered abnormal and can cause
all of the user functions to lock up;
in this eventuality, an error message
"Er" is displayed permanently. The
error message "Er" is also displayed
to indicate a fault with the probe (open
contact or short circuit):
Alarm
Display
condition
Er
Water
temp:
˃45°C o
˂5°C
No flow alarm
Flow alarms are designed to protect the
heater from being activated in potentially
dangerous situations.
When the circulation pump is activated,
the flow of water must be detected by the
system in order to allow activation of the
heater.
When the circulation pump is active but
the system detects no flow, the heater is
disabled, the circulation pump remains
active, and the message "FLO" appears
in the display, alternating with the
temperature.
The "FLO" alarm condition can be reset
only by turning off and on the controller.
Low water level
If water is not detected by the level
sensor (L1) for more than 3 seconds
continuously, a low water level alarm is
tripped. All loads apart from the Light
Functions
Correction
inhibited
conditions
Heater
Temperature
deactivated
returns within
and user
permissible
load controls
range
inhibited
function (whirlpool pumps, blower,
circulation pump, heater and ozonator)
are disabled, and the message "LL"
appears in the display, alternating with
the temperature. The alarm resets
automatically once the correct water
level is restored.
Abnormally high temperature
In the event that the temperature of
the water should rise above 42 °C, all
loads will be disabled, and the message
"HI" appears in the display, alternating
with the temperature. The alarm resets
automatically and the loads will be re-
enabled once the temperature drops to
a value ≤ 40 °C:
Alarm
Display
condition
Water
HI
Heater and
temp:
all loads
˃42°C
deactivated.
User controls
inhibited
Water level control system
alarms
Unsuccessful drain timeout
When emptying the tub or pool and
the minimum level L1 is not detected
within 90 minutes of receiving the
control signal, the system locks up
on timeout and the message "AL1"
appears permanently in the display.
The alarm can be reset only by switching
off and rebooting the controller.
Unsuccessful replenish timeout
When replenishing the water level and
the passage from level L1 to level L2
(compensation tank) is not detected
within 90 minutes, the system locks
up on timeout and the message "AL2"
appears permanently in the display.
The alarm can be reset only by switching
off and rebooting the controller.
QUALITY STANDARDS
16
Functions
Correction
inhibited
conditions
Water
temperature
≤40°C