6 EN – Quick installation guide
Measure the insulation of the input and motor cables and
the motor
Step Task
1
Measure the insulation resistance of the input cable before you connect it to the drive.
Obey local regulations.
2
Ground the motor cable shield at the motor end. For minimal interference, make a
360-degree grounding at the cable entry, or keep the pig tail short.
EN
3
Measure the insulation resistance of the motor cable and motor when the cable is
disconnected from the drive. Measure the insulation resistance between each phase
conductor and the PE conductor. Use a measuring voltage of 1000 V DC. The insulation
resistance of an ABB motor must be more than 100 Mohm (reference value at 25 °C).
DA
For the insulation resistance of other motors, see the manufacturer's instructions.
Moisture inside the motor decreases the insulation resistance. If you think that there is
moisture, dry the motor and do the measurement again.
DE
Connect the power cables (and install the shrouds for
ES
option +B051)
See figure
G
on page 118.
FI
Step Task (motor cables)
1
Install the grounding terminal to the drive module base.
2
Run the motor cables to the enclosure. Ground the cable shields 360 degrees at the
FR
enclosure entry.
3
Connect the twisted shields of the motor cables to the grounding terminal.
4
Screw in and tighten the insulators to the drive module by hand. Install the T3/W2
IT
connection terminal to the insulators.
NL
5
Connect the phase T3/W2 conductors to the T3/W2 terminal.
PL
6
Install the T2/V2 connection terminal to the insulators. See the warning in step 4.
7
Connect the phase T2/V2 conductors to the T2/V2 connection terminal.
8
Install the T1/U2 connection terminal to the insulators. See the warning in step 4.
9
Connect the phase T1/U2 conductors to the T1/U2 terminal.
PT
10
Option +B051 (if there is no bottom plate in the enclosure and degree of protection of
IP20 is needed):
• Carefully step drill sufficiently big holes to the inner clear plastic shrouds for the motor
RU
cables to be connected. Smooth the hole edges. Cut the shroud from the holes to the
edge to make it possible to put the shroud around the cables.
• Remove the plastic sheeting from both sides of the shrouds.
SV
11
Option +B051: Put the inner clear plastic shrouds of figure
12
Option +B051: Remove the plastic sheeting from both sides of the output clear plastic
shroud. Install the shroud to the drive module.
TR
13
Option +B051: Install the lower front cover to the drive module.
Step Task (input cables)
ZH
1
Ground the input cable shields (if present) 360 degrees at the enclosure entry.
2
Connect the twisted shields of the input cables and separate ground cable (if present) to
the enclosure grounding busbar.
WARNING! Do not use longer screws or greater tightening torque than
given in the installation drawing. Doing either can damage the insulator
and cause dangerous voltage to be present at the module frame.
O
around the motor cables.
Figure Page
-
-
H
118
I
118
Figure Page
J
118
K
118
L
118
M
118
N
118
-
-
-
-
-
-
-
-
O
119
P
119
Q
119
Q
119
Figure Page
-
-
-
-

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Ach580-04

Inhaltsverzeichnis