1) Typical motor power with no overload capacity (nominal use). The kilowatt ratings apply to most IEC 4-pole motors.
The horsepower ratings apply to most NEMA 4-pole motors.
2) For IEC installations, ABB recommends aR fuses.
3) The recommended branch protection fuses must be used to maintain the IEC/EN/UL 61800-5-1 and CSA C22.2 No. 274 certifications.
4) IEC 61439-1: The drive is suitable for use on a circuit capable of delivering not more than 65 kA when protected by the fuses given in this
table.
5) IEC Installations: The cable sizing is based on max. 9 cables laid on a cable ladder side by side, three ladder type trays one on top of the
other, ambient temperature 30 °C, PVC insulation, surface temperature 70 °C (EN 60204-1 and IEC 60364-5-52/2001). For other
conditions, size the cables according to local safety regulations, appropriate input voltage and the load current of the drive.
6) Typical drive losses when it operates at 90% of the nominal output frequency and 100% of the motor nominal current. See IEC 61800-9-2.
ACH580-04-
Input
Output
...
current
current
IEC ratings
I
I
1
A
U
= 400 V
n
505A-4
505
485
585A-4
585
575
650A-4
650
634
725A-4
725
715
820A-4
820
810
880A-4
880
865
U
= 480 V
n
505A-4
483
483
585A-4
573
573
650A-4
623
623
725A-4
705
705
820A-4
807
807
880A-4
807
807
Terminal data
Screw size L1/U1, L2/V1, L3/W1, T1/U2, T2/V2, T3/W2 and UDC+, UCD- with +H356 and R+
Maximum accepted cable size
mm
M12
4 × (3 × 240)
Energy efficiency data (ecodesign)
Energy efficiency data according to IEC-61800-9-2 is available from the ecodesign tool.
(https://ecodesign.drivesmotors.abb.com).
Dimensions, weights and free space requirements
Frame size
Height
mm
IP00/IP20, UL Type Open/UL Type 1 (option +B051)
R10
1462
R11
1662
20 mm (0.79 in) free space is required around the drive module from the enclosure back panel and front door.
Motor
1)
power
P
LD
LD
DIN 43653
A
kW
250
170M6012
315
170M6014
355
170M6014
400
170M6016
450
170M6269
500
170M6269
400
170M6012
450
170M6014
500
170M6014
600
170M6016
700
170M6269
700
170M6269
and R- with +D150: full-size terminals
AWG
2
4 × (3 × 500) MCM
Width
in
mm
57.55
350
65.43
350
2)3)
aR fuses
(Bussmann)
cable (Copper)
4)
DIN 43620
170M8557D
170M8557D
170M8557D
-
-
-
170M8557D
170M8557D
170M8557D
-
-
-
Tightening torque
N·m
50...75
Depth
in
mm
13.78
529
13.78
529
Technical data 115
Typical power
Typical
5)
power loss
2
W
mm
3 × (3×95)
6492
3 × (3×120)
6840
3 × (3×150)
8046
3 × (3×185)
8108
3 × (3×240)
9652
3 × (3×240)
10887
3 × (3×95)
6492
3 × (3×120)
6840
3 × (3×150)
8046
3 × (3×185)
8108
3 × (3×240)
9652
3 × (3×240)
10887
Grounding terminal
Tightening torque
lbf·ft
N·m
37...55
20
Weight
in
kg
20.81
204
20.81
240
Frame
size
6)
R10
R10
R10
R11
R11
R11
R10
R10
R10
R11
R11
R11
lbf·ft
14.75
lb
449.7
529.11