Adjust the DIP switch 0 and C0034 for the same range, otherwise the
frequency inverter cannot interpret the analog input signal at X3/8.
If a setpoint potentiometer is internally supplied via X3/9, the DIP switch
must be set for a voltage range of 0 ... 5 V. This is necessary to cover the
complete speed range.
S g a to 3/8
Signal to X3/8
0 ... +5 V
0 ... +10 V (Lenze setting)
0 ... 20 mA
4 ... 20 mA
Open-circuit
4 ... 20 mA
monitoring
-10 V ... +10 V
l
I/O function module wiring
Internal voltage supply X3/20 (+20 V DC)
GND1
X3
62
AOUT1
External voltage supply + 24 V DC
(+12 V DC - 0 % ... +30 V DC + 0 %)
GND1
X3
62 7
AOUT1