4.3 Rooms with slanted and
horizontal ceilings
> 20°
Fig. 5
Straight mounting surface at least 1 m long and
1 m wide
Allowed
Not allowed
Note the following for straight mounting surface
less than 1 m long and 1 m wide:
f Observe chapter "Rooms with straight
ceilings (slope angle < 20°)" on page
41.
> 1,00
1/2
1/2
Operating Manual: PX-1 - Smoke Alarm Device
> 20°
Fig. 6
Straight mounting surface less than 1 m long and
1 m wide
Allowed
Not allowed
Note the following for straight mounting surface
less than 1 m long and 1 m wide:
f Observe chapter "Rooms with slanted
ceilings (slope angle > 20°)" on page
42.
< 1,00
43