4. Operating mode

Manual

In 'Manual' mode, the individual relay outputs and the connected consumers can be checked for proper functioning and correct
assignment.
The operating mode 'Manual' may only be used by specialists for brief function tests, e.g. during commissioning!
Functionality in manual mode: The relays and thus the connected consumers are switched on and off by pressing a
key, with no regard to the current temperatures and set parameters. At the same time, the current measurements of the
temperature sensors are also shown in the display for the purposes of function control.

Mode Heating Circuit

This sets the current heating circuit mode.
Off
'Off' should not switch between 'Heating' and 'Cooling', but should change automatically to heating off or cooling off depending on
the active season. 'Off' switches off the heating circuit, no matter what the room controllers indicate. If 'Off' is set via this parameter
or via Nabto, a change of mode on the room controller will not end the mode. Only the parameter in the controller itself or Nabto
can cancel this mode.
Heating
Heating switches the heating circuit mode to heating normal. However, the parameter also indicates 'Heating', if heating OFF,
heating eco, or heating turbo is active. Changes to room controllers or via Nabto can override the mode with one of the other
mode.

5. Settings

Heating Circuit

Settings see " Heating Circuit " on page 20

Heating Pump

Settings see " Heating Pump " on page 21.

Extra Pump

Settings see " Extra Pump " on page 23.
14
The basic settings for the control function of the heating circuit are applied.
The controller must never replace the safety appliances on site!