Installation procedure
L1: Total length of 22.22 liquid pipe; L2: Total length of 19.05 liquid pipe;
L3: Total length of 15.88 liquid pipe; L4: Total length of 12.7 liquid pipe;
L5: Total length of 9.52 liquid pipe; L6: Total length of 6.35 liquid pipe; Total refrigerant volume charging on
site during installation=W2+W3
W: Total refrigerant volume charging on site for maintenance.
Model
38VS226174HQEE
38VS280174HQEE
38VS335174HQEE
Note:
• To prevent a different oil from entering the pipe, please use the special tool prescribed for R410A,
especially for gauge manifold and charging hose.
• Mark the refrigerant type in a different colour on the tank. R410A is pink.
• Do not use the charging cylinder, because R410A will change when transferring to the cylinder.
• When charging refrigerant, it should be taken out from the tank in a liquid state.
• Mark the counted refrigerant volume due to the distributing pipe length on the label.
GWP: 2088
The product contains fluorinated greenhouse gases and its functioning relies on such gases.

Heat insulation

• The gas and liquid pipes should be heat insulated separately.
• The material for gas pipe should endure high temperatures
over 120
c .
o
• The material for liquid pipe should endure over 70
• The thickness should be over 10mm, when ambient temp. is
30
c, and when the relative humidity is over 80%, the thickness
o
Connection wire should be over 20mm.
• The material should cling to the pipe without leaving a gap and
should then be wrapped with adhesive tape. The connection
wire cannot be put together with the heat insulation material
and should over 20cm Adhesive tape be placed at least 20cm
away.
Fix the refrigerant pipe
• During operation, the pipe will vibrate and expand or shrink. If not fixed, the refrigerant will focus on one
part and damage the pipe.
• To prevent central stress, fix the pipe every 2-3m.
Refrigerant record form
W2:
W3: Refrigerant charging volume to liquid pipe base on
W1:
Refrigerant
Refrigerant
charging
charging volume
volume to
to outdoor unit at
outdoor unit
factory
on site
0kg
Refer to label
0kg
0kg
different piping length calculations
Liquid pipe diameter
Additional refrigerant
amount (kg)
(mm)
Ø
0.022kg/m× __m= __kg
6.35
Ø
9.52
0.054kg/m× __m= __kg
Ø
12.7
0.11kg/m× __m= __kg
Ø
15.88
0.17kg/m×__m= __kg
Ø
19.05
0.25kg/m× __m= __kg
Ø
22.22
0.35kg/m× __m= __kg
W3=
kg
c .
o
Liquid pipe
Liquid pipe
19
Total
W: Total
refrigerant
refrigerant
volume
volume
charging on
charging on
site for
site during
maintenance
installation
W2+W3=
W1+W2+
kg
W3=
kg
Connection wire
Connection wire
Over 20cm
over 20cm
Adhesive tape
Adhesive tape
Gas pipe
Gas pipe
Heat insulator
Heat insulator