Failure codes
Failure code
display on the
Failure code
outdoor digital
display
definition
boar
d
59
Tliqsc temp. sensor
failure
64
CT value too high
71-0
DC Fan1 failure
71-1
DC Fan2 failure
78
Lack of refrigerant
81
Inverter temp. too
high
82
Compressor current
protection
83
Model setting error
The inverter module
over current
110
(hardware)
Compressor out of
control
111
Failure code definition
Continuously disconnected for 60 seconds or
short circuit; failure alarm sounds.
When the CT current exceeds the specified
value for 5 consecutive seconds, failure alarm
sounds. The failure will be removed after 3
minutes. Failure is locked if it occurs thrice in
one hour.
The failure alarm will sound when it runs
below 20 rpm for 40 seconds or below 20%
of the target value for 2 minutes.
The failure will be removed after 3 minutes.
Failure is locked if it occurs thrice in one hour.
1.
Cooling: Ps=0.2MPa for 30 consecutive
minutes; failure alarm sounds. Ps > 0.3MPa
for 30 consecutive minutes; failure is
removed.
2.
Heating: Both LEVa equal to 470pls and Ts-
> 20C for 60 consecutive minutes; failure
Ps
> 0.2MPa for 30 consecutive
alarm sounds. Ps
Minutes; failure is removed.
Inverter temp. > 90 ° C, failure alarm sounds.
< 70
Inverter temp.
° C; failure is removed.
Failure is locked if it occurs thrice in one hour.
When the compressor current exceeds the
specified value for 5 consecutive seconds,
failure alarm sounds. The failure will be
removed after 3 minutes. Failure is locked if it
occurs thrice in one hour.
Model setting does not match the outdoor unit.
Module hardware over current. Failure is
locked if it occurs thrice in one hour.
Ins tantaneous over current of hardware at
the rectifier side of inverter module. Failure
is locked if it occurs thrice in one hour.
During s tart-up or operation, the rotor position
cannot be detected for 6 consecutive times;
failure alarm sounds. The inverter PCB will
recover automatically after compressor stops
for 5 seconds.
27
Remarks
Resumable
Once failure is
locked, non-
resumable.
Once failure is
locked, non-
resumable.
Resumable
Once failure is
locked, non-
resumable.
Once failure is
locked, non-
resumable.
Once failure is
locked, non-
resumable.
Once failure is
locked, non-
resumable.
Resumable