3.5 Connection to the compressed airline

Provide the throughput capacity of the compressed-air line in accordance with the perfor- mance
of the compressor. In order to avoid damage associated with seal failure of the compressed-air
line, the compressor should be connected via a flexible hose. All components of the com-
pressed-air line must have a working pressure no less than the compressor's nominal pressure.
Use a pressure vessel with a capacity corresponding to the compressor's performance and
the compressed air consumer.
3.6 Connecting to power supply
The compressor is not supplied with a power cable. The cable size must be chosen to ensure
that the maximum voltage drop not exceed 5 % of the nominal voltage value. Cable length
must not exceed 25 m. Ambient temperature in the facility must not exceed 40°C.
The cable must be sheathed with a fire retardant compound. An isolating switch must be
fitted within reach of the compressor to facilitate connection
The power cable has to be fed into the compressor.
Fig. 3.6.1 Power cable connection
COMPRAG
Screw air compressor DV-Series
The compressor must be earthed and protected against short
cir- cuits in each phase, impermissible voltage fluctuation and
phase failure.
2
1
and maintenance.
3
Fig. 3.6.2 Power cable terminal connection