0x9F - Detailed
Query:
Description and
Start Length
Example of "Re-
mote Ctrl CMD ID"
0x01
Remote Ctrl Data
Values in the 'Remote Ctrl Data' byte:
P
rel
P
rel
Reserved data must always be 0x00.
Response:
Start Length
Remote Ctrl Data
-
-
-
Inverter-specific behavior for Fronius IG Plus, Fronius CL, Fronius IG-TL, Fronius Agilo:
For effective power specified values < 10%, the inverter switches to 'Forced Standby' mode
– no power is fed into the grid.
NOTE! The extended reactive power range is only available in conjunction with
certain country setups.
Device / Op-
tion
0x09 +
0x00
Num-
ber of
invert-
ers
Inverter number
Remote Ctrl Data
Reserved Separator Reserved Reserved Separator Reserved
0x00
0x7F
0x00
: big endian | unsigned char | resolution: 1 LsB = 1 [%] | Value range 0d to 100d
Device / Op-
tion
variable 0x00
Inverter number
"P
" provides the maximum effective power output by the inverter in relation to the
rel
nominal power of the inverter.
A "P
" value of 100%, for example, means that the maximum effective power output
rel
by the inverter corresponds to the nominal power of the inverter - no limitations are in
effect.
A "P
" value of 10%, for example, means that the maximum effective power output
rel
by the inverter corresponds to 10% of the nominal power of the inverter.
Number
Com-
Remote Ctrl
mand
CMD ID
0x00
0x9F
0x01
Check-
sum
0x00
0x7F
Number
Com-
Remote Ctrl
mand
CMD ID
0x00
0x9F
0x01
Check-
sum
Separator
0x7F
0x00
Separator
0x7F
175