Cabling

Installing cabling
The data connection for the data communication components is a 1:1 connection using 8-
for data commu-
pin data cables and RJ 45 plugs.
nication compo-
nents
Requirements for
Shielded CAT5 (new) and CAT5e (old) cables compliant with ISO 11801 and EN50173
the data cables
must be used for the data communication component cabling. Other cables are not permit-
ted.
IMPORTANT! Do not use ISO/IEC-11801 U/UTP cables!
Permitted cables:
-
-
-
The shield must be crimped on to a CAT5-compatible shielded plug.
Due to the fact that the wires in Ethernet cables are twisted, you must make sure the twist-
ed pairs of wires are assigned correctly for cabling in accordance with EIA/TIA-568A:
Contact Fronius
1
2
3
4
5
6
7
8
Cabling compliant with EIA/TIA-568A
-
-
As a general rule, compliance with the following structured cabling standards must be en-
sured:
-
-
-
Rules for use of copper cables apply.
142
S/STP
F/STP
S/FTP
+12 V
GND
TX+ IN, RX+ OUT
RX+ IN, TX+ OUT
RX- IN, TX- OUT
TX- IN, RX- OUT
GND
+12 V
Make sure that the wires are assigned correctly.
When setting up an independent ground connection (e.g., in patch panels), make sure
that the shield is grounded on one side of the cable only.
EN50173-1 for Europe
ISO/IEC 11801:2002 internationally
TIA/EIA 568 for North America
-
F/FTP
-
SF/FTP
-
S/UTP
Pair no.
Color
3
3
2
1
1
2
4
4
-
F/UTP
-
U/FTP
-
U/STP
white / green line
green / white line
or green
white / orange line
blue / white line
or blue
white / blue line
orange / white line
or orange
white / brown line
brown / white line
or brown