TROUBLESHOOTING
Problem
No Restarting of
Outdoor Fan Motor
and Compressor
after Stoppage
for Cooling
Operation (Lamp
of "RUN" Switch
and Indicator is
Flickered)
Insufficient Cooling
(Lamp of "RUN"
Switch activates)
Insufficient Heating
(Lamp of "RUN"
Switch Activates)
(Only for Heat-
Pump Models)
Downloaded from
www.Manualslib.com
Causes
Obstacle to Air Intake of Air Discharge
for Outdoor Unit
Insufficient Air Intake or Air Discharge
Space for Outdoor Unit
Short Circuited Air Discharge for
Outdoor Unit
Tripped High Pressure
Faulty Outdoor Fan Motor
Switch
Overcharged Refrigerant
Clogged Capillary Tube
Excessively High Ambient
Temperature
Temperature of High Air Inlet
Temperature for Indoor Unit
Excessively High Discharge or Suction
Pressure
High or Low Voltage
Tripped Overcurrent
Faulty Compressor Motor (After
relay for Compressor
Checked Electrical Resistance)
Motor
Faulty Overcurrent Relay
Faulty Starting Relay
Frequent start/stop compressor
Excessive Cooling Load
Insufficiently Charged Refrigerant Gas
Refrigerant Gas Leakage
Clogged Strainer
Clogged Suction Piping
Too Low Pressure
Clogged Air Filter
Obstacle to Air Intake or Air Discharge
for Indoor Unit
Faulty Indoor Fan Motor
Short Circuited Air Discharge for
Indoor Unit
Excessively High
Same as Tripped Air Discharge for
Pressure
Indoor Unit
Clogged Strainer
Clogged Suction Piping
Obstacle to Air Intake or Air Discharge
for Outdoor Unit
Too Low Pressure
Faulty Outdoor Fan Motor
Short Circuited Air Discharge for
Outdoor Unit
Faulty Thermistor(s) for Deicer
Excessively High
Same as Tripped Air Discharge for
Pressure
Indoor Unit
manuals search engine
Solution
Remove the obstacle
Keep the minimum Air Intake and Air Discharge Space
Remove Any Obstacle
Replace the Outdoor Fan Motor
Charge Correct Refrigerant Gas
Replace the Capillary Tube
See Unit Working Range
Reduce the Cooling Load
Same as Tripped High Pressure Switch Remedy Action
Obtain Correct Voltage
Replace the Compressor
Replace the Overcurrent Relay
Replace the Starting Relay
Replace the compressor
Reduce the Cooling Load
Charge Correct Refrigerant Gas
Repair Leakage and Charge Correct Refrigerant Gas
Repair or Replace the Strainer
Remove the Obstacle
Cleaning the Air Filter
Take Away the Obstacle
Replace the Indoor Fan Motor
Take Away any Obstacle
Same as Tripped High Pressure Switch Remedy Action
Repair or Replace the Strainer
Remove the Obstacle
Take away the obstacle
Replace the Outdoor Fan Motor
Take Away any Obstacle
Replace the Thermistor(s)
Same as Tripped High Pressure Switch Remedy Action
PMGB0126A rev.2 - 11/2006