ELECTRICAL WIRING

13. ELECTRICAL WIRING
GENERAL CHECK
1. Ensure that the field-supplied electrical components (mains
power switches, circuit breakers, wires, connectors and
wire terminals) have been properly selected according to
the electrical data indicated. Make sure that they comply
with national and regional electrical codes.
2. Check to ensure that the power supply voltage is within
+/-10% of the rated voltage.
3. Check to ensure that power supply has an impedance low
enough to warranty not reduce the starting voltage more
than 85% of the rated voltage.
4. Check to ensure that the ground wire is connected.
5. Connect a fuse of specified capacity.
DANGER:
Do not connect of adjust any wiring or connections unless
-
the main power switch is OFF.
Check that the earth wire is securely connected, tagged
-
and locked in accordance with national and local codes.
NOTE:
Check and test to ensure that if there is more than one
-
source of power supply, that all are turned OFF.
Downloaded from
www.Manualslib.com
manuals search engine
6. Following the Council Directive 89/336/EEC and its
amendments 92/31/EEC and 93/68/EEC, relating
to electromagnetic compatibility, next table indicates
maximum permissible system impedance Zmax at the
interface point of the user's supply, in accordance with
EN61000-3-11
MODEL
RASC-5HNE
RASC-10HNE
CAUTION:
Check to ensure that the indoor fan and the outdoor fan
-
have stopped before electrical wiring work or periodical
check is performed.
Protect the wires, drain pipe, electrical parts, from rats or
-
other small animals. If not protected, rats may damage
unprotected parts, and at the worst, a fire will occur.
-
Wrap the accessory packing around the wires, and
plug the wiring connection hole with the seal material
to protect the product from any condensed water and
insects.
Tightly secure the wires with the cord clamp inside the
-
indoor unit.
Lead the wires through the knockout hole in the side
-
cover when using conduit.
Secure the cable of the remote control switch with the
-
cord clamp inside the electrical box.
Electrical wiring must comply with national and local
-
codes. Contact your local authority in regards to
standards, rules, regulations, etc.
Check that the ground wire is securely connected.
-
Connect a fuse of specified capacity.
PMDE0126A rev.2 - 11/2006
Z
(Ω)
MAX
0.21
0.12
23