TROUBLESHOOTING
Troubleshooting
Problem
No Activation of
Unit Operation
Indicator
No Activation of
Compressor and
Fan Motor (In the
Case of Indicator
Activation of
Remote Control
Switch)
Flickering of
Indicator and Lamp
of "RUN" Switch
No Speed Change
of Fan In spite of
Adjustment
No Stopping
and Starting of
Compressor In
spite of Adjusting
Thermostat
Downloaded from
www.Manualslib.com
Causes
Electrical Power Source Failure
Electrical Short Circuit to Earth
Blow off Main
Faulty Compressor Motor
Switch Fuse
Faulty Indoor Fan Motor
Electrical Short Circuit between Different Phase
Wires
Blow off
Control
Electrical Short Circuit to Earth
Circuit Fuse
Faulty Magnetic Switch for Compressor Motor
Faulty Transformer of Indoor Unit
Disconnected Cable of Remote Control Panel to the Indoor Unit
Abnormality of Remote Control Switch
Incorrect
Disconnected Wire(s) to PCB of Indoor Unit
activation of
Faulty PCB of Indoor Unit
PCB
Faulty Indoor Fan Motor
Faulty Outdoor Fan Motor
Faulty magnetic switch for Outdoor Fan Motor
Faulty Compressor Motor of Compressor
Faulty Magnetic Switch for Compressor Motor
Disconnected Wire(s) to PCB
Incorrect activation of PCB
Faulty PCB of Indoor Unit
In case of 3~ unit installed
for first time, if an "05" code
Phase protection Relay
is indicated on remote
control switch
Faulty Internal Thermostat for Indoor Fan Motor
Disconnected Wires between Indoor Unit and Outdoor Unit
Disconnected Wire(s) to the PCB
Incorrect Activation of PCB
Faulty PCB of Indoor Unit
Tripped Float Switch for Drain (only in RCI Units)
Faulty Thermistor
Abnormality of Thermistor
for Air Inlet Discharge Temp.
Disconnected Wire of Thermistor
Faulty Remote Control Switch
Faulty PCB of Indoor Unit
Faulty Thermistor
Abnormality of Thermistor
for Air Inlet Temperature
Disconnected Wire of Thermistor
Faulty "TEMP" Switch of Remote Control Switch
Faulty PCB of Indoor Unit
Faulty Cable of Remote Control Switch
manuals search engine
Solution
Wait for Recovering of Electrical Power Supply
Replace the Main Switch Fuse after Eliminating
Earthing
Replace the Compressor and the main Switch Fuse
Replace the indoor Fan Motor and the Main Switch
Fuse
Replace the Fuse
Replace the Fuse
Replace the magnetic Switch and the Fuse
Replace the Transformer
Replace the Cable
Check the connection of the Remote Control Cable.
Replace the Remote Control Switch.
Connect Wire(s) to the PCB
Replace the PCB of Indoor Unit
Replace the Indoor Fan Motor
Replace the Outdoor Fan Motor
Replace the magnetic switch of the Outdoor Unit
Replace the Compressor
Replace the magnetic switch
Connect Wire(s) to the PCB
Replace the PCB for Indoor Unit
Switch off the power supply of the unit, reverse 2 of
the phases, reapply the power and restart the unit
Replace the Indoor Fan Motor
Connect the Wires Correctly
Connect Wire(s) to the PCB
Replace the PCB for Indoor Unit
Adjust level of the Drain pan Repair or Replace the
Drain Discharge Mechanism. Remove the Clogged
Material
Replace the Thermistor
Connect the Wire to the Thermistor
Replace the Remote Control Switch
Replace the PCB of the Indoor Unit
Replace the Thermistor
Connect the Wire of Thermistor
Replace "TEMP" Switch of Remote Control Switch
Replace PCB of the Indoor Unit
Replace the Cable
PMGB0126A rev.2 - 11/2006
34