Informationen zur elektrischen Installation
Anschluss nach UL
Absicherungsdaten
Absicherungsdaten
Branch Circuit Protection (BCP)
Short Circuit Current Ratings (SCCR) with Standard Fuses and Circuit Breaker
(Tested per UL61800-5-1, reference UL file E132659)
These devices are suitable for motor group installation when used with Standard Fuses or Cir-
cuit Breaker. For single motor installation, if the fuse value indicated is higher than 400 % of
the motor current (FLA), the fuse value has to be calculated. If the value of the fuse is below
two standard ratings, the nearest standard ratings less than the calculated value shall apply.
Inverter
Mains
Rated power
kW
120 V, 1-ph
0.37
120 V, 1-ph
0.75
120 V, 1-ph
1.1
230 V, 1-ph
0.37
230 V, 1-ph
0.55
230 V, 1-ph
0.75
230 V, 1-ph
1.1
230 V, 1-ph
1.5
230 V, 1-ph
2.2
230 V, 1/3-ph
0.37
230 V, 1/3-ph
0.37
230 V, 1/3-ph
0.55
230 V, 1/3-ph
0.75
230 V, 1/3-ph
1.1
230 V, 1/3-ph
1.5
230 V, 1/3-ph
2.2
230 V, 3-ph
3
230 V, 3-ph
4
230 V, 3-ph
5.5
230 V, 3-ph
7.5
230 V, 3-ph
11
230 V, 3-ph
15
230 V, 3-ph
18.5
480 V, 3-ph
0.37
480 V, 3-ph
0.37
480 V, 3-ph
0.55
480 V, 3-ph
0.75
480 V, 3-ph
1.1
480 V, 3-ph
1.5
480 V, 3-ph
2.2
480 V, 3-ph
3
480 V, 3-ph
4
480 V, 3-ph
5.5
480 V, 3-ph
7.5
480 V, 3-ph
11
480 V, 3-ph
15
480 V, 3-ph
18.5
480 V, 3-ph
22
600 V, 3-ph
0.75
600 V, 3-ph
1.5
600 V, 3-ph
2.2
52
Standard Fuses (UL248)
SCCR
Max. rated current
HP
kA
0.5
5
1
5
1.5
5
0.5
65
0.75
65
1
65
1.5
65
2
65
3
65
0.5
65
0.5
65
0.75
65
1
65
1.5
65
2
65
3
65
4
5
5
5
7.5
5
10
5
15
5
20
5
25
5
0.5
65
0.5
65
0.75
65
1
65
1.5
65
2
65
3
65
4
5
5
5
7.5
5
10
5
15
5
20
5
25
5
30
5
1
5
2
5
3
5
Class
A
30
CC, CF, J, T
30
CC, CF, J, T
30
CC, CF, J, T
60
CF, J, T
60
CF, J, T
60
CF, J, T
60
CF, J, T
60
CF, J, T
60
CF, J, T
60
CF, J, T
60
CF, J, T
60
CF, J, T
60
CF, J, T
60
CF, J, T
60
CF, J, T
60
CF, J, T
80
CF, J, T
80
CF, J, T
80
CF, J, T
80
CF, J, T
80
CF, J, T
125
CF, J, T
125
CF, J, T
60
CF, J, T
60
CF, J, T
60
CF, J, T
60
CF, J, T
60
CF, J, T
60
CF, J, T
60
CF, J, T
50
CF, J, T
50
CF, J, T
50
CF, J, T
50
CF, J, T
50
CF, J, T
80
CF, J, T
80
CF, J, T
80
CF, J, T
20
CC, CF, J, T
20
CC, CF, J, T
20
CC, CF, J, T
Circuit Breaker (UL489)
SCCR
Max. rated current
kA
A
5
30
5
30
5
30
5
30
5
30
5
30
5
30
5
30
5
30
5
30
5
30
5
30
5
30
5
30
5
30
5
30
5
30
5
30
5
30
5
30
5
30
5
30
5
30