Sicherheitshinweise für die Installation nach UL
Motor Overload Protection
– For information on the protection level of the internal overload protection
for a motor load, see the corresponding manuals or software helps.
– If the integral solid state motor overload protection is not used, external or
remote overload protection must be provided.
Branch Circuit Protection
– The integral solid state protection does not provide branch circuit
protection.
– Branch circuit protection has to be provided externally in accordance with
corresponding instructions, the National Electrical Code and any
additional codes.
Please observe the specifications for fuses and screw−tightening torques in
these instructions.
EVS9321 … EVS9326:
– Suitable for use on a circuit capable of delivering not more than 5000 rms
symmetrical amperes, 480 V maximum, when protected by fuses.
– Suitable for use on a circuit capable of delivering not more than 50000 rms
symmetrical amperes, 480 V maximum, when protected by CC, J, T or R
class fuses.
– Maximum surrounding air temperature: 0 ... +55 °C
– > +40 °C: reduce the rated output current by 2.5 %/°C
– Use 75 °C copper wire only.