Display text

|Communication error|

|Alarm level|
|Temperature error|
Is a potential-free contact activated, if yes, which? (W = warning, E = error)
1
Error message, backwater technology
Display text
|Motor error|
|Motor error, extension
flap|
|Flap error |
|Flap error, extension
flap|
Is a potential-free contact activated, if yes, which? (W = warning, E = error)
1
3
1
4
1
46 / 148
PFC
Possible cause
3
E
Telecontrol modem error
Error in the potential-free contact/serial
connection
W
Level exceedance detected
E
Temperature exceedance on the printed
board
PFC
Possible cause
4
E
Cable break or motor faulty
E
Cable break or the redundant control
unit's motor is defective
E
Flap cannot be closed completely, i.e.
the flap is blocked by an object
Backwater has been detected and the
flap cannot be closed completely, i.e. the
flap is blocked by an object
E
Redundant closure cannot be closed
completely, i.e. the flap is blocked by an
object
Backwater has been detected and the
flap cannot be closed completely, i.e. the
flap is blocked by an object
Installation and operating instructions
Remedial measure
no network/credits, no connection to the
modem, equipment fault
If it occurs frequently, check the design
and performance of the pump(s).
Establish the specified ambient conditions
for the control unit, see "Technical data",
page 29
Remedial measure
Disconnect the system from the mains
power supply, disable the battery, check
the cable for correct connection and con-
tinuity; test the function of the motor,
replace if necessary
Disconnect the system from the mains,
disable the battery; check the cable for
correct connection and continuity, test the
function of the motor, replace redundant
control unit motor if necessary.
Pull out the mains plug, disconnect the
battery, open the flap cover and remove
the blockage and restart the system
Close the emergency closure (hinged flap,
if present). Following the end of backwa-
ter, eliminate the blockage as described
above. To install the flap cover, the flap
motor must be in the CLOSED position.
Pull out the mains plug at the redundant
closure of the control unit, disconnect the
battery; open the flap cover, remove the
blockage and restart the system
Following the end of backwater remove
the blockage as described above