BTS M30E0-_ _ _-H0001-S04G
Infrared Temperature Sensor
9
Configuring the Digital Outputs
The digital outputs can be configured independently of each other. The settings options for all the digital outputs are
the same. The submenu OUT1/OUT2 shows an overview of the settings currently in effect.
How to navigate in the menu:
► Use [▲], [▼] to select the desired setting.
► Use [↵] to switch to the submenu.
9.1
The digital outputs work by default in two-point mode. The state of each digital output is determined by two swit-
ching thresholds, an upper and a lower switching threshold. Both switching thresholds thus define the hysteresis. The
minimum hysteresis is 1% of the detection range.
Normally Open
Normally Closed
9.2
The values for the turn-on and turn-off switching threshold can be set independently of each other.
1
www.balluff.com
Downloaded from
www.Manualslib.com
Switching Mode
Lower detection range end value
0 %
OUT/BDC
LO
Lower
switching threshold ≥ 0 %
OUT/BDC
LO
Setting the Turn-on and Turn-off Switching Threshold
manuals search engine
Upper detection range end value
Detection range
Upper
switching threshold ≤ 100 %
Hysteresis
≥ 1 %
2
100 %
HI
Temperature value
HI
Temperature value
1
Current setting in effect
3
2
Select the new desired
setting with [▲] or [▼]
2
3
Possible change direc-
tion
english
19