BTS M30E0-_ _ _-H0001-S04G
Infrared Temperature Sensor
9
Configuring the Digital Outputs
9.5
The upper switching thresholds of the digital outputs can be taught independently of each other. A static teach-in
procedure is used with two teach points. The switching threshold results, after successful teaching, from the setting
of both teach points.

Teach-in

1. Use [↵] to confirm teach-in and start the teach-in
routine.
⇒ The screen then guides you through the teach-in
2. Align the sensor with the object and use [↵] to
confirm.
⇒ Teach point 1 (TP1) is learned.
3. Remove the object from the detection range and use
[↵] to confirm.
⇒ Teach point 2 (TP2) is learned.
The upper switching threshold is set between the object
(TP1) and the background (TP2). The lower switching
threshold is set by 1% of the detection range below the
upper switching threshold.
If the switching thresholds are not within the detection
range or TP2 (background) is not less by 1% than TP1
(object), the teach-in procedure is ended with an error
indication and the old switching thresholds remain in
effect.
4. Check the taught switching thresholds and confirm with [↵] .
⇒ The switching thresholds are now saved and in effect.
www.balluff.com
Downloaded from
www.Manualslib.com
Teach-in
routine.
Note
TP2 (background) must be at least 1% of the detection range less than TP1 (object).