BTS M30E0-_ _ _-H0001-S04G
Infrared Temperature Sensor
15
IO-Link Interface
15.8
Principle
Switchpoint SPy is determined by teaching two teach points (TP1 and TP2).
Function:
Result:
BDCx
Teach-In Status
Example for:
0 = TP1 of SP2 not taught or not successful
1 = TP1 or SP2 successfully taught
www.balluff.com
Downloaded from
www.Manualslib.com
Teach-In Switchpoints via IO-Link
Note
Teach-In is automatically left 10 min after starting. During this time no teach-in can be started from the opera-
ting keys.
TP1 = Teaching static object
TP2 = Teaching background
SPy lies between the object and the background
Two Value Teach
TP2
SPy
TP1
1
0
T
x = 1, 2 y =1, 2
Teach Flags
SP2
TP2
TP1
TP2
manuals search engine
System commands
SPy Two Value Teach TP1 (Set TP1)
SPy Two Value Teach TP2 (Set TP2)
Teach Apply (Set SPy)
SP1
TP1
0 = IDLE
1 = SP1 SUCCESS
2 = SP2 SUCCESS
3 = SP12 SUCCESS
Teach State
4 = WAIT FOR COMMAND
5 = BUSY
6 = reserved
7 = ERROR
english
39