BTS M30E0-_ _ _-H0001-S04G
Infrared Temperature Sensor
9
Configuring the Digital Outputs
The digital outputs can be configured independently of each other. The settings options for all the digital outputs are
the same. The submenu OUT1/OUT2 shows an overview of the settings currently in effect.
How to navigate in the menu:
► Use [▲], [▼] to select the desired setting.
► Use [↵] to switch to the submenu.
9.1
Switching Mode
The digital outputs work by default in two-point mode. The state of each digital output is determined by two swit-
ching thresholds, an upper and a lower switching threshold. Both switching thresholds thus define the hysteresis. The
minimum hysteresis is 1% of the detection range.
Lower detection range end value
0 %
OUT/BDC
Normally Open
LO
switching threshold ≥ 0 %
OUT/BDC
Normally Closed
LO
9.2
Setting the Turn-on and Turn-off Switching Threshold
The values for the turn-on and turn-off switching threshold can be set independently of each other.
1
www.balluff.com
All manuals and user guides at all-guides.com
Detection range
switching threshold ≤ 100 %
Hysteresis
≥ 1 %
Lower
2
Upper detection range end value
100 %
HI
Upper
Temperature value
HI
Temperature value
1
Current setting in effect
3
2
Select the new desired
setting with [▲] or [▼]
2
3
Possible change direc-
tion
english