ONNECTING THE
THE CONNECTION BETWEEN THE CPS AND THE BATTERY BOX MUST BE MADE WITH THE DEVICES
POWERED OFF AND UNPLUGGED FROM THE MAINS
CPS POWER-OFF PROCEDURE:
Turn off all devices connected to the CPS or use the remote bypass option (if installed).
Turn off the CPS following the relevant power-off procedure (see the "USE" section of the "Powering off the
CPS" paragraph).
Open all the isolators and fuse holders present in the CPS.
Isolate the CPS completely from the electricity network by opening all the external protective devices situated
on the input and output lines
Wait a few minutes before proceeding to work on the CPS.
Remove the terminal cover of the CPS (see "Operations to access the CPS/Battery Box terminals).
CONNECTING THE BATTERY BOX:
Check that the battery voltage of the Battery Box corresponds to that allowed by the CPS (check the data plate
on the Battery Box and the manual of the CPS)
IMPORTANT: make sure that the fuse holders of the CPS and the Battery Box are open.
Remove the terminal cover of the Battery Box (see "Operations to access the CPS/Battery Box terminals).
Connect the earth terminals of the CPS and the Battery Box.
Connect the terminals to the CPS and the Battery Box:
- terminals marked with the + symbol with the red cable
- terminals marked with the N symbol with the blue cable
- terminals marked with the – symbol with the black cable
respecting the correspondence indicated by the symbols print on the terminal cover of the Battery Box and the
CPS.
Reposition the terminal covers removed previously.

CHECKING INSTALLATION:

Insert the fuses in the SWBATT fuse holders of the Battery Box.
Close the SWBATT fuse holders of the Battery Box and the CPS.
Carry out the CPS power-on procedure described in this manual.
After about 30 sec., check that the CPS is working properly: simulate a black-out by opening the SWIN input
isolator of the CPS. The load must continue to be powered, the "battery power" LED must light up on the control
panel of the CPS, and the latter will emit a beep at regular intervals. When the SWIN input isolator is closed
again, the CPS must resume operation on mains power.