EDUNDANT
UXILIARY
The CPS is equipped with a redundant auxiliary power supply that enables the CPS to run on an automatic bypass even
when a failure occurs in the main auxiliary power supply. If a fault occurs in the CPS shutting off the main auxiliary power
supply, the load is powered by the automatic bypass. The multiprocessor board and the control panel are not powered so
the LEDs and the display are off.
A
UXILIARY SOCKETS
E
S
NERGY
HARE
Programmable output socket (optional) which allows automatic disconnection of the load applied to it under certain
operating conditions. Events that determine automatic disconnection of the EnergyShare socket can be selected by the
user through the configuration software. It is possible, for example, to select detachment after a certain period of battery
operation, or when the pre-alarm threshold for battery discharge has been reached, or when an overload occurs.
Notes regarding safety: if the output switch (SWOUT) is opened while the CPS is on, both sockets
remain powered.
If a manual bypass switch (SWMB) is inserted, the output switch (SWOUT) is opened and the CPS
switches off and both sockets will no longer be powered.
A
UX OUTPUT
Output socket (optional) directly connected to the CPS output; It caters auxiliary power supply (230V / max 10A)
P
-
OWER WALK
IN
The CPS has a Power Walk-in mode which can be enabled and configured using the configuration software. When the
mode is enabled and mains power is restored after a period of battery operation, the CPS starts to draw progressively
from it so as not to stress (due to the peak) any generating set installed upstream. The transient time may be set from 1
to 125 seconds. The default value is 10 seconds (when this function is active). During the transient, the necessary power
is drawn in part from the batteries and in part from the mains, maintaining sinusoidal absorption. The battery charger is
turned on again once the transient has passed.
P
S
OWER
UPPLY FOR
(
)
OPTIONAL
- 94 -
A
B
UTOMATIC
YPASS