S
CPS
TORING THE
The storage room must respect the following conditions:
Temperature:
Relative humidity:
P
REPARING FOR INSTALLATION
P
I
RELIMINARY
NFORMATION
Modelli CPS
Rated power
Working temperature
Max. relative humidity during operation
Max. height of installation
W x D x H
w/o batteries
Weight
w/ batteries
Power dissipated at rated resistive load
(pf=0.9) and with battery as buffer *
Power dissipated at rated distortion
load (pf=0.7) and with battery charged *
Flow rate of fans for removing heat from
installation room **
Current leak to earth ***
Isolation protection
Cable input
*
3.97 B.T.U./h = 1 kcal/h
** The following formula can be used to calculate the fan capacity: Q [mc/h] = 3.1 x P diss [kcal/h] / (t a - t e ) [°C]
P diss is the dissipated power of all the installed apparatus at the installation premises expressed in kcal/h.
ta= environmental temperature, te= external temperature. To account for leaks, increase the value obtained by 10%.
The table shows an example of the fan capacity with (t a - t e )=5°C and with nominal resistive load (pf=0.9).
(N.B.: The formula applies if ta>te; otherwise an air conditioner should be installed).
*** The dispersion current of the load is added to the dispersion current of the CPS on the earth protection conductor.

INSTALLATION

B
AND THE
ATTERY
0°÷40°C (32°÷104°F)
max. 95%
1603 B.T.U./h
1263 B.T.U./h
B
OX
CPS 6
6000 VA
90 % (non-condensing)
1000 m at rated power
(-1% Power for every 100 m above 1000 m)
max 4000 m
440 x 850 x 1320 mm
105 Kg
315 Kg
0.47 kW
404 kcal/h
540 kcal/h
2150 B.T.U./h
0.37 kW
318 kcal/h
420 kcal/h
1670 B.T.U./h
250 mc/h
From bottom / on rear
- 68 -
CPS 10
CPS 15
10000 VA
15000 VA
0 ÷ 40 °C
110 Kg
320 Kg
0.63 kW
0.86 kW
740 kcal/h
2940 B.T.U./h
0.49 kW
0.67 kW
580 kcal/h
2290 B.T.U./h
340 mc/h
460 mc/h
< 7 mA
IP20
120 Kg

Werbung