Preliminary Operations - Gtec CPS 6 Handbuch

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

P
O
RELIMINARY
Visual check of the connection
Check that all the connections have been made strictly following the indications given in the "Connections"
paragraph.
Check that the "1/0" button is in its "0" position (see "Front Views of the CPS" point 5).
Check that all the isolators are open.
Close the battery fuse holders
Close the 4 battery fuse holders (SWBATT) present in the position indicated in the figure below.
Note: The equipment is protected against battery inversion (for further details see "Battery anti-inversion
device")
CAUTION: In the event that the batteries are connected to the battery terminals with the polarity
inverted, this device will protect the CPS by interrupting the battery connections.
As the fuses are being closed, a small electric arc caused by the capacitors inside the CPS may be
generated. This is quite normal and not the result of malfunctions and/or breakage.
Power on the CPS
Close the protective devices upstream from the CPS.
Close the input and output isolators
Close all input disconnectors (SWIN), output disconnectors, (SWOUT) and separate bypass disconnectors
(SWBYP) except for the maintenance disconnector (SWMB), which should remain open.